E-FSC Series

Conventional Fire Alarm Control Panels

Description

Note:  E-FSC series panels have been replaced by FX series conventional panels (FX-5 and FX-10)

The E-FSC Series fire alarm family consists of 3, 5 and 10 zone conventional fire alarm control panels, an integrated DACT/Dialer, serial annunciator modules, and serial remote relay modules. All of these components are microprocessor-controlled. The E-FSC Series family is ideal for both new and retrofit installations alike.

E-FSC Series incorporates features designed to simplify installation, operation and maintenance. These include front panel programming, one person walk testing, and selectable IDC and NAC types.

E-FSC Series panels are powerful enough to meet the demands of today’s installations while leaving plenty of room to grow in the future.

E-FSC502 and E-FSC1004 panels support Class A operation by combining pairs of on-board IDCs or NACs to provide the necessary Class A circuits. For example, the E-FSC1004 comes factory set to support 10 Class B IDCs and four NACs. But it can be field-configured to provide five Class A IDCs, no Class B IDCs, and two Class A NACs – or any other combination of circuits that fall within the circuit-pairing parameters.



  • Available in 3, 5, and 10 IDC models

  • IDC or NAC pairs convertible to single Class A circuits (10 and 5 IDC panels only)

  • Combination Waterflow and Supervisory IDCs

  • NACs programmable by zone and individually selectable for Genesis, continuous, temporal outputs, or coded

  • Front panel programmable simplifies installation and servicing PC programmable with optional DACT installed

  • Genesis option allows precision synchronization and audible silence over two wires without additional modules

  • On-board relays for Alarm, Supervisory and Trouble

  • Optional serial bus relay modules are programmable for common or zone activation

  • Optional serial bus remote annunciator family

  • One person walk-test (audible or silent)

  • Expandable power supply on 10 IDC panel reduces booster power costs

  • Optional City Tie and Reverse Polarity Modules

  • Trim ring available for semi-flush mounting

  • Optional fully integrated DACT/Dialer for PC programming

  • Supports Edwards ED2M, SC and 2400 series detectors and ESL 400, 500 and 700 series detectors

E-FSC Series

Link to this product

Catalog Numbers

Purchase from the Edwards on-line store or Locate a distributor in your area
Enter your Zip Code:
Catalog Number
Description
  12V10A

11 Ah Sealed Lead Acid Battery - 12 Vdc
12 Vdc, 11 Ah

$145.18
  12V17A

18 Ah Sealed Lead Acid Battery - 12 Vdc
12 Vdc, 18 Ah

$207.34
  12V4A

4.5 Ah Sealed Lead Acid Battery - 12 V dc

$114.24
  12V6A5

7.2 Ah Sealed Lead Acid Battery - 12 Vdc
12 Vdc, 72. Ah

$130.34
  CTM

City Tie Module

$265.72

Specifications

Approvals

Agency Approvals

  • UL Listed

  • ULC Listed

  • CSFM Listed


 

Specifications

E-FSC1004 Series

  • Power Supply: 4.25 amps expandable to 8.5 amps
  • NAC Voltage Rating: 24V FWR
  • Maximum NAC current: 2.0 amps each, 3.5 amps total; 7.0 amps w/ optional transformer
  • AC Input
    • 120V AC 50/60 Hz: 2.2 amps w/ optional transformer
  • Base Panel Current Draw
    • Standby: 128 mA
    • Alarm: 242 mA
  • Panel Battery Charge Capacity (sealed lead acid only): Up to two 24 Ah batteries, 10 Ah in cabinet
  • Auxiliary Current: 0.5 amps max. May be programmed as resettable.
  • Auxiliary Output: 21.2 to 25.7 Vdc
  • IDC Alarm Current: 3.0 mA (Consult detector compatibility list p/n 3100468 for maximum detectors per circuit)
  • IDC Circuit:
    • Maximum loop resistance: 13 Ohms
    • Maximum loop capacitance: 0.03 microF
  • IDC Operating Voltage: 16.3 to 28 Vdc
  • UL Detector ID: 100
  • Alarm Contact (Form C): 30 Vdc @ 1 A (resistive load)
  • Trouble Contact (Form C): 30 Vdc @ 1 A (resistive load)
  • Supervisory Contact (Form C): 30 Vdc @ 1 A (resistive load)
  • Operating Environment
    • Temperature: 32 - 120F (0 - 49C)
    • Humidity: 5 - 93% RH, non-condensing
  • Terminals (wire gauge): 18 - 12 AWG (0.75 mm² - 2.5 mm²)
  • Asynchronous Serial Communications
    • Maximum resistance: 13 Ohms
    • Maximum capacitance: 0.03 microF



E-FSC502 Series

  • Power Supply: 4.25 amps total
  • NAC Voltage Rating: 24V FWR
  • Maximum NAC current: 2.0 amps each, 3.5 amps total
  • AC Input
    • 120V AC 50/60 Hz: 1.25 amps
  • Base Panel Current Draw
    • Standby: 104 mA
    • Alarm: 224 mA
  • Panel Battery Charge Capacity (sealed lead acid only): Up to 24 Ah, 7Ah max in cabinet *
  • Auxiliary Current: 0.5 amps max. May be programmed as resettable.
  • Auxiliary Output: 21.2 to 25.7 Vdc
  • IDC Alarm Current: 3.0 mA (Consult detector compatibility list p/n 3100468 for maximum detectors per circuit)
  • IDC Circuit:
    • Maximum loop resistance: 13 Ohms
    • Maximum loop capacitance: 0.03 microF
  • IDC Operating Voltage: 16.3 to 28 Vdc
  • UL Detector ID: 100
  • Alarm Contact (Form C): 30 Vdc @ 1 A (resistive load)
  • Trouble Contact (Form C): 30 Vdc @ 1 A (resistive load)
  • Supervisory Contact (Form C): 30 Vdc @ 1 A (resistive load)
  • Operating Environment
    • Temperature: 32 - 120F (0 - 49C)
    • Humidity: 5 - 93% RH, non-condensing
  • Terminals (wire gauge): 18 - 12 AWG (0.75 mm² - 2.5 mm²)
  • Asynchronous Serial Communications
    • Maximum resistance: 13 Ohms
    • Maximum capacitance: 0.03 microF



E-FSC302 Series

  • Power Supply: 4.25 amps total
  • NAC Voltage Rating: 24V FWR
  • Maximum NAC current: 2.0 amps each, 3.5 amps total
  • AC Input
    • 120V AC 50/60 Hz: 1.25 amps
  • Base Panel Current Draw
    • Standby: 96 mA
    • Alarm: 180 mA
  • Panel Battery Charge Capacity (sealed lead acid only): Up to 24 Ah, 7Ah max in cabinet *
  • Auxiliary Current: 0.5 amps max. May be programmed as resettable.
  • Auxiliary Output: 21.2 to 25.7 Vdc
  • IDC Alarm Current: 3.0 mA (Consult detector compatibility list p/n 3100468 for maximum detectors per circuit)
  • IDC Circuit:
    • Maximum loop resistance: 13 Ohms
    • Maximum loop capacitance: 0.03 microF
  • IDC Operating Voltage: 16.3 to 28 Vdc
  • UL Detector ID: 100
  • Alarm Contact (Form C): 30 Vdc @ 1 A (resistive load)
  • Trouble Contact (Form C): 30 Vdc @ 1 A (resistive load)
  • Supervisory Contact (Form C): 30 Vdc @ 1 A (resistive load)
  • Operating Environment
    • Temperature: 32 - 120F (0 - 49C)
    • Humidity: 5 - 93% RH, non-condensing
  • Terminals (wire gauge): 18 - 12 AWG (0.75 mm² - 2.5 mm²)
  • Asynchronous Serial Communications
    • Maximum resistance: 13 Ohms
    • Maximum capacitance: 0.03 microF