Intelligent Addressable Duct Smoke Detector
E-PDD / FX-PDD
Description
The E-PDD part number has been replaced by FX-PDD. Products are otherwise identical.
|
Link to this product
|
Catalog Numbers
Catalog Number
![]() |
Description
![]() |
![]() |
Specifications
Approvals
Agency Approvals- UL Listed
- ULC Listed
- CSFM Listed
Detector Specifications
- Communication line voltage: Maximum 20 V peak-to-peak
- Operating current:
- Normal: 45 ìA
- Alarm: 45 ìA
- Inrush: 1 mA
- Common alarm relay/auxiliary equipment: Unsupervised and power-limited Quantity: 1 Type: Form C Rating: 2.0 A at 30 VDC (resistive)
- Air velocity: 100 to 4,000 ft./min
- Air pressure differential: 0.005 to 1.00 inches of water
- Smoke sensitivity range: 0.79 to 2.46%/ft. obscuration
- Smoke detection method: Photoelectric (light scattering principle)
- Alarm test response time: 5 seconds
- Dimensions: 8.70 x 5.45 x 1.90 inches
- Operating environment:
- Temperature: 32 to 120 °F (0 to 50 °C)
- Humidity: 0 to 93% RH, noncondensing
- Wire size: 14 to 22 AWG wire
- Detector address
- 01 to 64 (64 point control panel)
- 01 to 127 (127 point control panel)
- Accessories:
- Remote test-reset station, magnetic: SD-TRM
- Remote test-reset station, keyed: SD-TRK
- Test magnet: SD-MAG
- Air velocity test kit: SD-VTK
- Remote LED alarm indicator: R-LED
Test station specifications
Remote Test/Reset Stations provide alarm test, trouble indication, and reset capability from a remote location. They include a one-gang plate, momentary SPST switch, red alarm LED, and terminal block. Magnetically-operated models (TRM) or key-operated models (TRK) are available.
- Compatible electrical boxes:
- North American 1-gang box
- Standard 4-in square box, 1-1/2 inches deep, with 1-gang cover
- LED indicators: Alarm (red)
- LED type: Clear lens
- Wire size: 14 to 22 AWG
- Resistance per wire: 10 Ohms, max.
- Current requirements: See controller specifications
- LED circuit ratings: Voltage: 3 Vdc, max. Current: 30 mA, max.
- Switch ratings (SD-TRK): Voltage: 125 Vdc, max. Current: 4 A, max.
- Switch ratings (SD-TRM): Voltage: 200 Vdc, max. Current: 0.5 A, max.
- Operating environment:
- Temperature: 32 to 120 °F (0 to 50 °C)
- Humidity: 93% RH, noncondensing
- Storage temperature-: 4 to 140 °F (-20 to 60 °C)
Documentation
Fire Alarm Sales Tools
- Edwards Signaling Smoke and Heat Detectors Application Bulletin
This is a guide for the installation of smoke and heat detectors.
- FX-PDD Addressable Duct Smoke Detector Installation Sheet
- R02_E-SDPCB_Duct_Smoke_Detector_PCB_Replacement_Kit_Installation_Sheet.pdf
- Product_Bulletin 052316 E-PDD Replacement Edwards
This bulletin announces the replacement for the E-PDD addressable duct detector.