E-PD, E-PHD, E-HD
Intelligent Addressable Detectors & Bases
Description
|
Detector Details & Application
E-PHD Optical/Fixed Temperature Detector
The SB4U is field-configurable for output tone (steady or temporal) and output volume (low dBA or high dBA). The base must be connected to a continuous voltage whether the output tone is set to steady or temporal. The base does not require a separate address because it shares the address of the device it is connected to. |
Link to this product
|
Catalog Numbers
| Catalog Number
|
Description
|
|||||||
Specifications
Approvals
Agency ApprovalsE-PHD
- UL 268
- ULC-S529-02
- UL 521
- ULC-S530-M91
- NFPA 72
- CAN/ULC S524-01
E-PD
- UL 268
- ULC-S529-02
- NFPA 72
- CAN/ULC S524-01
E-HD
- UL 521
- ULC-S530-M91
- NFPA 72
- CAN/ULC S524-01
Detectors
E-PHD
- Air velocity: 0 to 5000 ft/min (0 to 25.39 m/s)
- Smoke sensitivity range: 0.67% - 3.66%
- ULI fixed-temp alarm rating: 135F (57C)
- ULC fixed-temp alarm rating: 140F (60C)
- Operating voltgae: 15.2 to 19.95V DC
- Normal operating current: 45 microAmps, average
- Alarm current: 45 microAmps, average
- Environmental compensation: Automatic
- Compatible bases: B4U Standard, RB4U Relay, IB4U Isolator, SB4U Audible
- Maximum distance from ceiling wall-mounted: 12 in. (305 m)
- Storage tempertaure: -4 to 140F (-20 to 60C)
- Operating environment:
- Temperature: 32 to 120F (0 to 49C)
- Humidity: 0 to 93% RH, noncondensing at 90F (32C)
E-PD
- Air velocity: 0 to 5000 ft/min (0 to 25.39 m/s)
- Smoke sensitivity range: 0.67% - 3.66%
- Operating voltgae: 15.2 to 19.95V DC
- Normal operating current: 45 microAmps, average
- Alarm current: 45 microAmps, average
- Environmental compensation: Automatic
- Compatible bases: B4U Standard, RB4U Relay, IB4U Isolator, SB4U Audible
- Maximum distance from ceiling wall-mounted: 12 in. (305 m)
- Storage tempertaure: -4 to 140F (-20 to 60C)
- Operating environment:
- Temperature: 32 to 120F (0 to 49C)
- Humidity: 0 to 93% RH, noncondensing at 90F (32C)
E-HD
- ULI fixed-temp alarm rating: 135F (57C)
- ULC fixed-temp alarm rating: 140F (60C)
- Maximum Spacing: 50 ft (15 m) centers)
- Operating voltgae: 15.2 to 19.95V DC
- Normal operating current: 45 microAmps, average
- Alarm current: 45 microAmps, average
- Environmental compensation: Automatic
- Compatible bases: B4U Standard, RB4U Relay, IB4U Isolator, SB4U Audible
- Maximum distance from ceiling wall-mounted: 12 in. (305 m)
- Storage tempertaure: -4 to 140F (-20 to 60C)
- Operating environment:
- Temperature: 32 to 120F (0 to 49C)
- Humidity: 0 to 93% RH, noncondensing at 90F (32C)
Bases
B4U Standard Base
- Operating environment:
- Temperature: 32 to 120F (0 to 49C)
- Humidity: 0 to 93% RH, noncondensing at 90F (32C)
- Storage temperature range: -4 to 140F (-20 to 60C)
- Compatible detectors: E-PD, E-PHD, E-HD
- Compatible electrical boxes:
- North American 2 1/2 in. (64 mm) deep, 2 gang box
- Standard 4 in. square box 1 1/2 in. (38 mm) deep box
- Wire size: 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0 or 0.75 sq. mm) (Sizes 16 and 18 AWG are preferred)
- Base diameters: 6.0 in. (152 mm)
- Height from box (including detector): 2.08 in. (53 mm)
- Maximum distance from ceiling (wall mount): 12 in. (305 mm)
IB4U Isolator Detector Base
- Operating environment:
- Temperature: 32 to 120F (0 to 49C)
- Humidity: 0 to 93% RH, noncondensing at 90F (32C)
- Storage temperature range: -4 to 140F (-20 to 60C)
- Compatible detectors: E-PD, E-PHD, E-HD
- Compatible electrical boxes:
- North American 2 1/2 in. (64 mm) deep, 2 gang box
- Standard 4 in. square box 1 1/2 in. (38 mm) deep box
- Wire size: 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0 or 0.75 sq. mm) (Sizes 16 and 18 AWG are preferred)
- Base diameters: 6.0 in. (152 mm)
- Height from box (including detector): 2.57 in. (65 mm)
- Maximum distance from ceiling (wall mount): 12 in. (305 mm)
RB4U Relay Detector Base
- Operating environment:
- Temperature: 32 to 120F (0 to 49C)
- Humidity: 0 to 93% RH, noncondensing at 90F (32C)
- Storage temperature range: -4 to 140F (-20 to 60C)
- Compatible detectors: E-PD, E-PHD, E-HD
- Compatible electrical boxes:
- North American 2 1/2 in. (64 mm) deep, 2 gang box
- Standard 4 in. square box 1 1/2 in. (38 mm) deep box
- Wire size: 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0 or 0.75 sq. mm) (Sizes 16 and 18 AWG are preferred)
- Base diameters: 6.0 in. (152 mm)
- Height from box (including detector): 2.57 in. (65 mm)
- Maximum distance from ceiling (wall mount): 12 in. (305 mm)
SB4U Audible Detector Base
- Operating voltage: 24V DC or 24V FWR, nominal
- Operating current: refer to Data Sheet
- Supervisory current: DC = 1.46 mA, FWR = 2.15 mA
- Default settings:
- Output volume: High dBA
- Output tone: Temporal pattern
- Sound level output: Refer to Data Sheet
- Temporal pattern: 0.5s on, 0.5s off, 0.5s on, 0.5s off, 0.5s on, 1.5s off, repeat cyce
- Operating environment:
- Temperature: 32 to 120F (0 to 49C)
- Humidity: 0 to 93% RH, noncondensing at 90F (32C)
- Storage temperature: -4 to 140F (-20 to 60C)
- Compatible detectors: E-PD, E-PHD, and E-HD detectors
- Compatible electrical boxes:
- North American 2 1/2 in. (64 mm) deep, 2 gang box
- Standard 4" square box 1 1/2 in. (38 mm) deep box
- Wire size: 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm) (Sizes 16 and 18 AWG are preferred)
- Base diameter: 6.0 in. (152 mm)
- Height from box (including detector): 2.58 in. (66 mm)
- Maximum distance from ceiling (wall mount): 12 in. (305 mm)
Documentation
- Fire Alarm Product Guide
A guide for the Edwards fire alarm products, including the E-FSC conventional panels, E-FSA addressable panels, initiating devices, signaling devices, and accessories.
Data Sheets
Installation Instructions
- B4U_Analog_Standard_Detector_Base_Installation_Sheet.pdf
- RB4U_Analog_Relay_Detector_Base_Installation_Sheet.pdf
- IB4U_Analog_Isolator_Detector_Base_Installation_Sheet.pdf
- E-HD_Fixed-Temperature-Rate-of-Rise_Heat_Detector_Installation_Sheet.pdf
- SB4U_Analog_Audible_Detector_Base_Installation_Sheet.pdf
- R-LED_Remote_Alarm_Indicator_Installation_Sheet.pdf
- E-PD_Photoelectric_Smoke_Detector_Installation_Sheet.pdf
- E-PHD_Photoelectric_and_Fixed_Temperature_Heat_Detector_Installation_Sheet.pdf
- AE Bulletin 091311_Sounder Base Wiring.pdf
Tips on how to wire and supervise the power to SB4U addressable sounder bases.
- Sounder Base Programming
Tips on how to program (turn on) the addressable SB4U sounder base.
- Tech Bulletin, Smoke Supervisory Configuration Fault
An explanation of a configuration fault caused by programming a smoke detector as a supervisory input using the FSA-CU, and how to resolve.