E Series

Intelligent Addressable Input Output Modules

Description

Edwards intelligent modules are engineered to deliver high-performance features, superb reliability, and unbeatable quality. From control of ancillary equipment, to enhanced signaling functionality, these products add flexibility and powerful options to Edwards Signaling intelligent systems.


Designed expressly for small buildings, Edwards Signaling modules are addressable devices that are uniquely identifi ed on the system by means of familiar rotary switches. Once registered, they share data and update status information that determines how the system behaves and how connected devices interact with one another.


Unique to Edwards Signaling modules is ground fault detection so precise that it actually pinpoints the specific module where the wiring problem has occurred. This saves hours of troubleshooting and
wire tracing. And only Edwards Signaling provides this important feature!


The Edwards Signaling family of intelligent modules also offers contractors and installers simple setup and installation, while delivering options that take full advantage of intelligent fire alarm processing. With a microprocessor in each device, intelligence is distributed throughout the system so that command decisions are made instantly at the individual module, rather than bottlenecking at the control panel.


This not only speeds event processing, it also makes a more robust and reliable system – so robust, in fact, that when upgrading from a conventional panel to a Edwards Signaling intelligent system, you can usually use existing wiring – no twisted or shielded cable required!

E-2WIRE Class A-B Two-Wire Module
Acts as an interface between conventional two-wire smoke detectors and the Edwards Signaling control panel.

E-IDC1A Analog Class A Single Input Module
Used to connect a normally open, alarm, supervisory, or monitor type dry contact initiating device circuit to the Edwards Signaling control panel.

E-IDC2B Analog Dual Input Module
Connects two normally open, alarm, supervisory, or monitor type dry contact initiating device circuits to the Edwards Signaling control panel.

E-IDCWS Analog Dual Input Waterflow, Supervisory Module
Used to connect normally open waterfl ow alarm and supervisory initiating device circuits to the Edwards Signaling control panel. For Class B circuit operation.

E-ISO Analog SLC Fault Isolator Module
Protects a Class A SLC from total collapse due to wire-to-wire short circuits.

E-NAC Analog NAC Module
Connects a supervised output circuit to a signal riser.

E-RLY Analog Contact Relay Module
Provides one Form C dry relay contact and can be configured to provide polarity reversal of its output.

E-IDC1B Analog Single Input Mini Module
Connects a normally open, alarm, supervisory, or monitor type dry contact initiating device circuit (IDC) to the Edwards Signaling control panel. For Class B circuit operation.

E Series

Link to this product

Specifications

Approvals

Agency Approvals

  • UL Listed

  • ULC Listed

Specifications

E-IDC1B: Single Input Mini Module
The E-IDC1B connects a normally open, alarm, supervisory, or monitor type dry contact initiating device circuit (IDC) to the Edwards Signaling control panel. This module is for Class B circuit operation.
The device address is set using the two rotary switches located on the front of the module. One device address is required.

The module is configured to operate as an alarm latching device type from the factory. When the NO contact of an initiating device is closed, an alarm signal is sent to the control panel and the alarm condition is latched at the module.

Additional device types are available through front panel programming or the configuration utility. Refer to applicable control panel technical reference manual.

  • Communication line voltage: Maximum 20V peak-to-peak
  • Current:
    • Standby: 350 microA
    • Activated: 500 microA
  • Ground fault impedance: 10 K ohm
  • Operating environment:
    • Temperature: 32 to 120F (0 to 49C)
    • Humidity: 0 to 93% RH, noncondensing at 90F (32C)
  • Storage temperature range: -4 to 140F (-20 to 60C)
  • Compatible electrical boxes:
    • North American 4 inch square x 2 1/2 in. (64 mm) deep, 2 gang box
    • Standard 4 in. square box, 1 1/2" (38 mm) deep box
  • Wire size: 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm) (Sizes 16 and 18 AWG are preferred)
  • Device address (two addresses required):
    • 01 to 64 (64 point control panel)
    • 01 to 127 (127 point control panel)
  • Initiating device circuit (IDC):
  • EOL resistor value: 47 K ohm (P/N: EOL-47)
  • Max. circuit resistance: 50 ohms (25 ohms per wire)
  • Max. circuit capacitance: 0.1 microF



E-IDC2B: Dual Input Module
The E-IDC2B connects two normally open, alarm, supervisory, or monitor type dry contact initiating device circuits (IDCs) to the Edwards Signaling control panel. This module is designed for Class B circuit operation.

The device address is set using the two rotary switches located on the front of the module. Two consecutive addresses are required. The second address is automatically assigned one number higher than the value set on the rotary switches.

The E-IDC2B can be preset for alarm or supervisory operation using the slide switch located on the front of the module. It can also be configured for other device types through front panel programming or the configuration utility.

  • Communication line voltage: Maximum 20V peak-to-peak
  • Current:
    • Standby: 550 microA
    • Activated: 725 microA
  • Ground fault impedance: 10 K ohm
  • Operating environment:
    • Temperature: 32 to 120F (0 to 49C)
    • Humidity: 0 to 93% RH, noncondensing at 90F (32C)
  • Storage temperature range: -4 to 140F (-20 to 60C)
  • Compatible electrical boxes:
    • North American 4 inch square x 2 1/2 in. (64 mm) deep, 2 gang box
    • Standard 4 in. square box, 1 1/2" (38 mm) deep box
  • Wire size: 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm) (Sizes 16 and 18 AWG are preferred)
  • Device address:
    • 01 to 63 (64 point control panel)
    • 01 to 126 (127 point control panel)
  • Initiating Device Circuit:
    • EOL resistor value: 47 Kohm (P/N: EOL-47)
    • Max. circuit resistance: 50 ohms (25 ohms per wire)
    • Max. circuit capacitance: 0.1 microF



E-IDCWS: Dual Input Waterflow, Supervisory Module
The E-IDCWS connects normally open waterflow alarm and supervisory initiating device circuits (IDCs) to the Edwards Signaling control panel. The E-IDCWS is designed for Class B circuit operation.

The device address is set using the two rotary switches located on the front of the module. Two consecutive addresses are required. The second address is automatically assigned one number higher that the value set on the rotary switches.

The E-IDCWS can operate in the following modes:
Waterflow

  • Alarm latching delayed: Configures the module for use with only nonretarded waterflow alarm switches. When the NO input contact of an initiating device is closed, an alarm is sent to the control panel, which after a 16 second time delay, generates an alarm signal.



Supervisory

  • Supervisory active nonlatching US marketplace
  • Supervisory active latching Canadian marketplace
  • Nonlatching: Configures the module for normally open dry contact initiating devices. When the NO input contact of an initiating device is closed, a supervisory signal is sent to the control panel and the supervisory condition is not latched at the module.
  • Latching: Configures the module for normally open dry contact initiating devices. When the NO input contact of an initiating device is closed, a supervisory signal is sent to the control panel and the supervisory condition is not latched at the module.

 

  • Communication line voltage: Maximum 20V peak-to-peak
  • Current:
    • Standby: 550 microA
    • Activated: 725 microA
  • Operating environment:
    • Temperature: 32 to 120F (0 to 49C)
    • Humidity: 0 to 93% RH, noncondensing at 90F (32C)
  • Storage temperature range: -4 to 140F (-20 to 60C)
  • Compatible electrical boxes:
    • North American 4 inch square x 2 1/2 in. (64 mm) deep, 2 gang box
    • Standard 4 in. square box, 1 1/2" (38 mm) deep box
  • Wire size: 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm) (Sizes 16 and 18 AWG are preferred)
  • Device address:
    • 01 to 63 (64 point control panel)
    • 01 to 126 (127 point control panel)
  • Initiating Device Circuit:
    • EOL resistor value: 47 Kohm (P/N: EOL-47)
    • Max. circuit resistance: 50 ohms (25 ohms per wire)
    • Max. circuit capacitance: 0.1 microF



E-IDC1A: Class A Single Input Module
The Class A Single Input Module is used to connect a normally open, alarm, supervisory, or monitor type dry contact initiating device circuit (IDC) to the Edwards Signaling control panel. The module is designed for Class A circuit operation.

The module's device address is set using the two rotary switches located on the front of the module. One device address is required.

The device can be preset for alarm or supervisory operation using the slide switch located on the front of the module. The module can also be configured for other device types through front panel programming or the configuration utility.

  • Communication line voltage: Maximum 20V peak-to-peak
  • Current:
    • Standby: 400 microA
    • Activated: 500 microA
  • Operating environment:
    • Temperature: 32 to 120F (0 to 49C)
    • Humidity: 0 to 93% RH, noncondensing at 90F (32C)
  • Storage temperature range: -4 to 140F (-20 to 60C)
  • Compatible electrical boxes:
    • North American 4 inch square x 2 1/2 in. (64 mm) deep, 2 gang box
    • Standard 4 in. square box, 1 1/2" (38 mm) deep box
  • Wire size: 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm) (Sizes 16 and 18 AWG are preferred)
  • Device address:
    • 01 to 64 (64 point control panel)
    • 01 to 127 (127 point control panel)
  • Initiating Device Circuit:
    • Max. circuit resistance: 50 ohms (25 ohms per wire)
    • Max. circuit capacitance: 0.1 microF



E-2WIRE: Class A-B Two-Wire Module
The E-2WIRE module interfaces between conventional two-wire smoke detectors and the Edwards Signaling control panel. It monitors the circuit and smoke detectors, and signals the control panel of any trouble or alarm conditions. The module also regulates and supervises the 24 VDC input power.

The E-2WIRE is configured to operate as a two-wire alarm device that does not require alarm verification. It can be set for two-wire alarm verified operation through front panel programming or the configuration utility. When using the alarm verification feature of the control panel, do not mix normally open contact initiating devices with two-wire conventional smoke detectors.

This module recognizes the CleanMe signal from detectors that support this feature.
The device address is set using the two rotary switches located on the front of the module. One device address is required.

The E-2WIRE can be set for Class B or Class A operation using the slide switch located on the front of the module.

Note: This module cannot be used on a device loop with isolator modules or isolator bases.

  • Communication line voltage: Maximum 20.6V peak-to-peak
  • Current:
    • Standby: 350 microA
    • Activated: 350 microA
  • Control panel input power: 12.4 to 28.3V DC (not resettable)
  • Smoke power current:
    • Standby: 17 mA
    • Alarm: 58 mA
  • Smoke detector current: 3 mA
  • UL compatibility ID: 0.0
  • Ground fault impedance: 5 Kohm
  • Operating environment:
    • Temperature: 32 to 120F (0 to 49C)
    • Humidity: 0 to 93% RH, noncondensing at 90F (32C)
  • Storage temperature range: -4 to 140F (-20 to 60C)
  • Compatible electrical boxes:
    • North American 4 inch square x 2 1/2 in. (64 mm) deep, 2 gang box
    • Standard 4 in. square box, 1 1/2" (38 mm) deep box
  • Wire size: 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm) (Sizes 16 and 18 AWG are preferred)
  • Device address:
    • 01 to 64 (64 point control panel)
    • 01 to 127 (127 point control panel)
  • Initiating Device Circuit:
    • EOL resistor value: 4.7 Kohm (P/N: EOL-4.7)
    • Max. circuit resistance: 50 ohms (25 ohms per wire)
    • Max. circuit capacitance: 0.1 microF



E-RLY: Contact Relay Module
The E-RLY provides one Form C dry relay contact. It can also be configured to provide polarity reversal of its output. The E-RLY can be used to control external appliances or shut down equipment.

The E-RLY is wired according to its operation. It is configured to operate as a relay nonsilence device type, and can function as either a control relay or polarity reversal relay, depending on how it is wired.
Control relay function: Provides one Form C dry relay contact.

Polarity reversal relay function: Provides polarity reversal of its output.

Note: Additional device types are available through front panel programming or the configuration utility. Refer to applicable control panel technical reference manual.

  • Communication line voltage: Maximum 20V peak-to-peak
  • Current:
    • Standby: 125 microA
    • Activated: 125 microA
  • contact ratings (pilot duty):
    • 30V DC: 2A
    • 125V AC: 0.5A resistive load 60W or 62.5VA max
  • Relay type: Form C, programmable
  • Operating environment:
    • Temperature: 32 to 120F (0 to 49C)
    • Humidity: 0 to 93% RH, noncondensing at 90F (32C)
  • Storage temperature range: -4 to 140F (-20 to 60C)
  • Compatible electrical boxes:
    • North American 4 inch square x 2 1/2 in. (64 mm) deep, 2 gang box
    • Standard 4 in. square box, 1 1/2" (38 mm) deep box
  • Wire size: 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm) (Sizes 16 and 18 AWG are preferred)
  • Device address (one address required):
    • 01 to 64 (64 point control panel)
    • 01 to 127 (127 point control panel)



E-NAC: NAC Module
The E-NAC connects a supervised output circuit to a signal riser. The output wiring is monitored for open and short circuits. A short circuit causes the module to inhibit the activation of the audible/visual signal circuit so the riser is not connected to the wiring fault. Upon command from the control panel, the module connects the output circuit to the riser input. The output circuit energizes a riser to operate polarized audible and visual signals. The module can be used for connection of a Class A or Class B (with EOL) output notification appliance circuit (NAC).

The E-NAC is configured to operate as a Genesis Audible/Visual/Silence device type from the factory. It can also be configured for other device types through front panel programming or the configuration utility. Refer to the applicable control panel technical reference manual for a list of available device types.
Genesis Audible/Visual/Silence: Used with Genesis and Enhanced Integrity horns and strobes. Signals maintain synchronization per UL 1971. For Genesis devices, this configuration allows connected horns to be silenced while strobes on the same two-wire circuit continue to flash until the panel is reset.

  • Communication line voltage: Maximum 20V peak-to-peak
  • Current:
    • Standby: 350 microA
    • Activated: 200 microA
  • Ground fault impedance: 10 Kohm
  • Operating environment:
    • Temperature: 32 to 120F (0 to 49C)
    • Humidity: 0 to 93% RH, noncondensing at 90F (32C)
  • Storage temperature range: -4 to 140F (-20 to 60C)
  • Output ratings:
    • Circuit current: 24V DC at 2A max.

EOL resistor value: 47 Kohm UL Listed


  • Compatible electrical boxes:
    • North American 4 inch square x 2 1/2 in. (64 mm) deep, 2 gang box
    • Standard 4 in. square box, 1 1/2" (38 mm) deep box
  • Wire size: 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm) (Sizes 16 and 18 AWG are preferred)
  • Device address (one address required):
    • 01 to 64 (64 point control panel)
    • 01 to 127 (127 point control panel)



E-ISO: SLC Fault Isolator Module
The E-ISO protects a Class A SLC from total collapse due to wire-to-wire short circuits. The module monitors line voltages and opens the SLC when a short is detected. A short is isolated between the two modules located electrically closest to the short.

The device address is set using the two rotary switches located on the front of the module. One device address is required.

  • Communication line voltage: Maximum 20V peak-to-peak
  • Current:
    • Standby: 175 microA
    • Activated: 200 microA
  • Ground fault impedance: 10 Kohm
  • Maximum circuit resistance between isolators: 6 ohm
  • Operating environment:
    • Temperature: 32 to 120F (0 to 49C)
    • Humidity: 0 to 93% RH, noncondensing at 90F (32C)
  • Storage temperature range: -4 to 140F (-20 to 60C)
  • Compatible electrical boxes:
    • North American 4 inch square x 2 1/2 in. (64 mm) deep, 2 gang box
    • Standard 4 in. square box, 1 1/2" (38 mm) deep box
  • Wire size: 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm) (Sizes 16 and 18 AWG are preferred)
  • Device address:
    • 01 to 64 (64 point control panel)
    • 01 to 127 (127 point control panel)